Zeror.ai Error Codes Siemens F00041

Siemens F00041

Brand: SiemensModel: SINAMICS G120Error code: F00041

What the Fault Means

Fault: Motor Data Identification Failure

Likely causes

  • r0949 = 0: Load missing
  • r0949 = 1: Current limit level reached during identification.
  • r0949 = 2: Identified stator resistance less than 0.1% or greater than 100%.
  • r0949 = 3: Identified rotor resistance less than 0.1% or greater than 100%.
  • r0949 = 4: Identified stator reactance less than 50% and greater than 500%
  • r0949 = 5: Identified main reactance less than 50% and greater than 500%
  • r0949 = 6: Identified rotor time constant less than 10ms or greater than 5s
  • r0949 = 7: Identified total leakage reactance less than 5% and greater than 50%
  • r0949 = 20: Identified IGBT on-voltage less than 0.5 V or greater than 10 V
  • r0949 = 30: Current controller at voltage limit
  • r0949 = 40: Inconsistence of identified dataset, at least one identification failed
  • r0949 = 41: Writing of calculated magnetizing current P0320 failed
  • r0949 = 42: Writing of identified stator resistance failed
  • r0949 = 43: Writing of identified rotor resistance P0354 failed
  • r0949 = 44: Writing of identified rotor time constant P0622 failed
  • r0949 = 45: Writing of identified mutual reactance P0360 failed
  • r0949 = 46: Writing of identified stator leakage reactance P0356 failed
  • r0949 = 47: Writing of identified rotor leakage reactance P0358 failed
  • r0949 = 48: Writing of identified on voltage P1825 failed.
  • r0949 = 49: Writing of the identified dead time compensation P1828 failed

Solution and Safe First Checks

  1. r0949 = 0: is the motor connected to the inverter.
  2. r0949 = 1-49: are the motor data in p0304 - p0311 correct.
  3. Check what type of motor wiring is required (star, delta).

Safety: do not work inside the panel without isolating the power; if unsure, consult a qualified technician.

Related Siemens error codes

Source: the Zeror.ai industrial fault database and Siemens technical documentation. This page is for information; on critical systems follow the manufacturer's manual and authorised service.