Zeror.ai Error Codes Siemens F13010

Siemens F13010

Brand: SiemensModel: SINAMICS G120 CU250S2Error code: F13010

What the Fault Means

Fault: Licensing function module not licensed

Likely causes

  • At least one function module which is under license does not have a license
  • Fault value (r0949, interpret hexadecimal): Bit x = 1: The corresponding function module does not have a license
  • Note: Refer to p0108 or r0108 for the assignment between the bit number and function module.

Solution and Safe First Checks

  1. enter and activate the license key for function modules under license (p9920, p9921).
  2. if necessary, de-activate unlicensed function modules (p0108, r0108).

Safety: do not work inside the panel without isolating the power; if unsure, consult a qualified technician.

Related Siemens error codes

Source: the Zeror.ai industrial fault database and Siemens technical documentation. This page is for information; on critical systems follow the manufacturer's manual and authorised service.

Siemens F13010 · Zeror.ai