Zeror.ai Error Codes Siemens F13102

Siemens F13102

Brand: SiemensModel: SINAMICS G120 CU250S2Error code: F13102

What the Fault Means

Fault: Know-how protection: Consistency error of the protected data

Likely causes

  • An error was identified when checking the consistency of the protected files
  • As a consequence, the project on the memory card cannot be run
  • Fault value (r0949, interpret hexadecimal): yyyyxxxx hex: yyyy = object number, xxxx = fault cause xxxx = 1: A file has a checksum error
  • xxxx = 2: The files are not consistent with one another

Solution and Safe First Checks

  1. Replace the project on the memory card or replace project files for download from the memory card.
  2. Restore the factory setting and download again.

Safety: do not work inside the panel without isolating the power; if unsure, consult a qualified technician.

Related Siemens error codes

Source: the Zeror.ai industrial fault database and Siemens technical documentation. This page is for information; on critical systems follow the manufacturer's manual and authorised service.

Siemens F13102 · Zeror.ai