Siemens F30081

Marca: SiemensModelo: SINAMICS G120 CU250S2Código de error: F30081

Qué Significa el Fallo

Fault: Power unit: Switching operations too frequent

Causas probables

  • closed-loop control is incorrectly parameterized.
  • motor has a short-circuit or fault to ground (frame).
  • U/f operation: Up ramp set too low.
  • U/f operation: rated current of motor much greater than that of power unit.
  • power cables are not correctly connected.
  • power cables exceed the maximum permissible length.

Solución y Primeras Comprobaciones Seguras

  1. check the motor data - if required, carry out commissioning.
  2. check the motor circuit configuration (star-delta)
  3. U/f operation: Increase up ramp.
  4. U/f operation: Check assignment of rated currents of motor and power unit.
  5. check the power cable connections.
  6. check the power cables for short-circuit or ground fault.

Seguridad: no trabajes dentro del cuadro sin cortar la energía; si tienes dudas, consulta a un técnico cualificado.