Marca: SiemensModelo: SINAMICS G120 CU250S2Código de error: F40825

Qué Significa el Fallo

Fault: CX32 DRIVE-CLiQ: Supply voltage failed

Causas probables

  • The DRIVE-CLiQ communication from the DRIVE-CLiQ component involved to the Control Unit signals that the supply voltage has failed
  • Fault cause: 9 (= 09 hex): The power supply voltage for the components has failed
  • Note regarding the message value: The individual information is coded as follows in the message value (r0949/r2124): 0000yyxx hex: yy = component number, xx = error cause

Solución y Primeras Comprobaciones Seguras

  1. carry out a POWER ON (switch-off/switch-on).
  2. check the supply voltage wiring of the DRIVE-CLiQ component (interrupted cable, contacts, ...).
  3. check the dimensioning of the DRIVE-CLiQ component power supply.

Seguridad: no trabajes dentro del cuadro sin cortar la energía; si tienes dudas, consulta a un técnico cualificado.