Marka: SiemensModel: SINAMICS G120 CU250S2Hata kodu: A01428

Hatanın Anlamı

Alarm: Topology: Incorrect connection used

Olası nedenler

  • The topology comparison has detected differences in the actual and target topologies in relation to one component
  • For a component, another connection was used
  • The different connections of a component are described in the alarm value
  • Alarm value (r2124, interpret hexadecimal): ddccbbaa hex: dd = connection number of the target topology (%4) cc = connection number of the actual topology (%3) bb = component class (% 2) aa = component number (%1) Note: Component class and connection number are described in F01375

Çözüm ve Güvenli İlk Kontroller

  1. reinsert the DRIVE-CLiQ cable to the component (correct the actual topology).
  2. adapt the project/parameterization in the commissioning software (correct the target topology).
  3. automatically remove the topology error (p9904).