Qué Significa el Fallo

Alarm: PROFINET: Consistency error affecting adjustable parameters

Causas probables

  • A consistency error was detected when activating the configuration (p8925) for the PROFINET interface
  • The currently set configuration has not been activated
  • Alarm value (r2124, interpret decimal): 0: general consistency error 1: error in the IP configuration (IP address, subnet mask or standard gateway) 2: Error in the station names
  • 3: DHCP was not able to be activated, as a cyclic PROFINET connection already exists

Solución y Primeras Comprobaciones Seguras

  1. check the required interface configuration (p8920 and following), correct if necessary, and activate (p8925).
  2. Reconfigure the station via the "Edit Ethernet node" screen form (e.g. with STARTER commissioning software).

Seguridad: no trabajes dentro del cuadro sin cortar la energía; si tienes dudas, consulta a un técnico cualificado.